top of page
< Back

LDM7 DC MCCB 1500V Non-Polarity

Application

  • The LDM7DC series DC molded case circuit breaker (referred to as circuit breaker) has a rated operating voltage to DC1500V.

  • Rated insulation voltage: 1500V.

  • Rated impulse withstand voltage: up to 12kV.

  • Rated current: 100A ~ 1600A.

  • The circuit breaker can be vertically or horizontally installed.

  • Compliance Standards: IEC 60947-1 and IEC 60947-2.

Working Conditions

  • Altitude: 2000m and below (high altitude capacity reduction coefficients apply above this).

  • Temperature:

    • Surrounding Medium: Not higher than +70°C (+45°C for Marine products) and not lower than -25°C.

    • Average Value (24h): Shall not exceed +35°C.

    • Note: For temperatures higher than +50°C, users must use capacity reduction coefficients.

  • Storage Temperature: -40°C ~ +75°C.

  • Humidity:

    • Relative humidity at installation site does not exceed 50% at a maximum temperature of +40°C.

    • Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C).

    • Special measures should be taken for occasional condensation due to temperature changes.

  • Inclination: The maximum inclination is ±22.5°.

  • Environment: * Must be used in a medium without explosion risk.

    • The medium must not be sufficient to corrode metal or destroy insulation gas and conductive dust.

    • Use where there is no rain and snow hit.